Features & Benefits
- Converts power from almost any AC source into computer-grade power
- Ferroresonant technology closely monitors sine wave purity
- External battery cabinets prolong backup time
- Incoming power is conditioned without depleting the battery, thereby conserving battery power for complete power outages
- Customizable receptacles, input plugs, voltage-matching transformers, and bypass switches provide compatibility with virtually any application
- Provided with free software bundle that includes LanSafe and FORESEER network monitoring software to ensure highest levels of data integrity
Product Snapshot
EATON FERRUPS UPS | |
---|---|
Power Rating | 500 VA to 18KVA |
Voltage | 120/208/240 |
Frequency | 60 Hz |
Configuration | Tower |
Product Series | Powerware |
General | |
---|---|
Models | 850VA / 1.4kVA / 3.1kVA / 5.3kVA |
Capacity (kVA/kW) | .85/.6, 1.4/1, 3.1/2.2, 5.3/3.7 |
Dimensions (inches) | 12x10x21.25 / 15.1x15.2x20.2 / 21.2x15.25x22.9 / 29.5x15.5x25 |
Typical (Full Load) | 11 / 14 / 14 / 20 |
Runtime: (Half Load)(minutes) | 28 / 37 / 35 / 50 |
Operation | |
Nominal Input Voltage | 102/208/240 |
Input Voltage Range | +15%, -20% |
Operating Frequency | 60 Hz Nominal (adjustable limits +_ 0.01 Hz to +_ 3Hz |
Nominal Output Voltage | 102/208/240 |
Output Voltage Regulation | ± 3% for input voltages of +15% to -20% |
Output Voltage THD | 5% or less at rated kW load |
Overload Capacity | 150% surge and 125% for10 min. on line, 150% surge and 110% for 10 minutes on inverter |
Transfer Time | 0 ms |
Lightning, Surge & Noise Protection | 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests. |
Common Mode – >120 dB. Normal Mode – >60dB | |
Efficiency | 85 / 88 / 91 / 90 |
Safety Certification | UL, CSA (cUL), Complies with European Low Voltage Directive 73/23/EEC |
EMI Compliance | FCC Class A, Complies with European Electromagnetic Compatibility Directve 89/336/EEC |
Testing Standards | ANSI/EEE C62.41 (1991); ANSI/EEE C62.45 (2002); EN62040-2 |
Communication | RS-232 serial port (DB-25), plus contact closures |
Environmental | |
Operating Temperature | 0 to 40° C |
Storage | -20° C to +60° C |
Relative Humidity | 0 to 95% without condensation |
Audible Noise at 1m | 47 / 49 / 51 / 51 |
Altitude | 3, 050m (10,000 ft.) maximum |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Industries & Applications
EATON FERRUPS TOWER UPS (Ferrups Uninterruptible Power Supply Systems)
FE500, FE700, FE850, FE1.15KVA, FE1.4KVA, FE2.1KVA, FE3.1KVA, FE4.3KVA, FE5.3KVA, FE7KVA, FE10KVA, FE12.5KVA, FE15KVA and FE18KVA
The EATON FERRUPS TOWER UPS (Ferrups Uninterruptible Power Supply Systems) is purpose-engineered for demanding applications such as 911 centers, global military installations, marine vessels, and other mission-critical applications that demand an industrial UPS system that is also a high quality power backup system for sensitive equipment. Applications include but are not limited to:
- Police & fire emergency call centers
- Military applications
- “Lights-out” or “dark factory” manufacturing
- Large data centers or IT systems
- Critical network switching & processing equipment
- Large-scale PLC controls